• DocumentCode
    1100943
  • Title

    Lightning Currents Flowing in the Soil and Entering a Test Power Distribution Line Via Its Grounding

  • Author

    Schoene, Jens ; Uman, Martin A. ; Rakov, Vladimir A. ; Jerauld, Jason ; Rambo, Keith J. ; Jordan, D.M. ; Schnetzer, G.H. ; Paolone, Mario ; Nucci, Carlo Alberto ; Petrache, Emanuel ; Rachidi, Farhad

  • Author_Institution
    EnerNex Corp., Knoxville, TN
  • Volume
    24
  • Issue
    3
  • fYear
    2009
  • fDate
    7/1/2009 12:00:00 AM
  • Firstpage
    1095
  • Lastpage
    1103
  • Abstract
    Current from nearby rocket-triggered lightning that flowed through the soil and into an unenergized test power distribution line was studied based on experimental data acquired in 2003 at the International Center for Lightning Research and Testing in Florida. The 15-pole, three-phase line was 812 m long, was equipped with four arrester stations, at poles 2, 6, 10, and 14, and was terminated in its characteristic impedance at poles 1 and 15. The neutral conductor of the line was grounded at each arrester station and at both line terminations. Measurements suggest that a significant fraction of the lightning current injected into the earth a distance of 11 m from pole 15 entered the line through the grounding system of pole 15. The peak value of the microsecond-scale return stroke current entering the line through the pole 15 line ground was 7% of the peak value of the return stroke current injected into the earth. The peak value of the millisecond-scale triggered lightning initial stage current and the millisecond-scale return-stroke and initial-stage charge transfer to the line through the pole 15 line ground was between 12% and 19% of the lightning peak current/charge transfer, indicating that the percentage values for the injected peak currents are dependent on the current waveshape: for microsecond-scale return stroke currents, possibly due to electromagnetic coupling effects, a smaller fraction of the current peak enters the line compared to millisecond-scale initial stage currents. In the latter case, any influence of electromagnetic coupling to the line on ground currents is expected to be negligible.
  • Keywords
    earthing; electromagnetic coupling; lightning protection; power distribution lines; power distribution protection; short-circuit currents; 15-pole three-phase line; International Center for Lightning Research and Testing; arrester station; electromagnetic coupling effect; grounding; lightning current; power distribution line; Arresters; Charge transfer; Conductors; Electromagnetic coupling; Grounding; Impedance; Lightning; Power distribution lines; Soil; Testing; Current measurements; electromagnetic coupling; grounding electrodes; grounds; lightning protection; power distribution lines; rocket-triggered lightning;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2009.2014031
  • Filename
    5109868