DocumentCode :
1101881
Title :
Relative Merits of Y and Delta Connection for Alternators
Author :
Eden, T.S.
Issue :
1
fYear :
1914
Firstpage :
803
Lastpage :
806
Abstract :
The main advantages obtained with the Y connection are as follows: (1) It is possible to bring out a lead from the neutral point of the winding, which is useful for various purposes. (2) The cost is less than with the delta connection, requiring approximately 58 per cent of the turns. (3) It is not possible for circulating currents of triple frequency to flow in the windings. The delta connection does not appear to have any advantages except as a convenience in design for certain voltages. When used, proper precautions must be exercised in the design to eliminate excessive circulating currents.
fLanguage :
English
Journal_Title :
American Institute of Electrical Engineers, Transactions of the
Publisher :
ieee
ISSN :
0096-3860
Type :
jour
DOI :
10.1109/T-AIEE.1914.4765158
Filename :
4765158
Link To Document :
بازگشت