DocumentCode
1101984
Title
The Electric Strength of Air-V
Author
Whitehead, J.B. ; Gorton, W.S.
Issue
1
fYear
1914
Firstpage
951
Lastpage
972
Abstract
The paper presents the account of an investigation of the influence of frequency on the corona, between 60 and 3000 cycles per second. The wire and coaxial cylinder method was used. A simple method for measuring the maximum value of an alternating voltage wave has been developed and used for obtaining this maximum value at the critical corona voltage. The gold-leaf electroscope was used to detect the first appearance of corona. It has been found that for frequencies above 275 cycles per second the corona voltage (maximum value) is not so uniform and constant as it is at frequencies in the neighborhood of 60 cycles. The indications of the investigation are that at 2000 cycles the corona voltage is lower than it is at 60 cycles by about 3 or 4 per cent. The experiments reveal several interesting instances of resonance phenomena in the high-tension transformer circuits.
fLanguage
English
Journal_Title
American Institute of Electrical Engineers, Transactions of the
Publisher
ieee
ISSN
0096-3860
Type
jour
DOI
10.1109/T-AIEE.1914.4765167