• DocumentCode
    1103156
  • Title

    Construction of 8000 A class 275 kV gas insulated transmission line

  • Author

    Kuroyanagi, Y. ; Toya, A. ; Hayashi, T. ; Araki, T.

  • Author_Institution
    Tokyo Electr. Power Co. Inc., Japan
  • Volume
    5
  • Issue
    1
  • fYear
    1990
  • fDate
    1/1/1990 12:00:00 AM
  • Firstpage
    14
  • Lastpage
    20
  • Abstract
    Class-8000 A 275 kV gas insulated transmission lines (GIL), 138 m and 158 m long, were completed as getaway lines in the Shin Noda substation of the Tokyo Electric Power Co. Inc. in March and May 1988, respectively. The GILs were designed for large current capacity. New techniques used to construct these lines are described. Thermal expansion and contraction of a straight section of a GIL is absorbed by varying the angle of a deflection unit. Supports were designed to absorb a ground depression. GIL units were installed with gantry cranes. Joints of enclosures were welded by an automatic welding machine
  • Keywords
    cable jointing; gaseous insulation; power transmission lines; substations; 138 m; 158 m; 275 kV; 8000 A; GIL; Shin Noda substation; Tokyo Electric Power Co. Inc.; automatic welding machine; gas insulated transmission lines; joints; supports; thermal contraction; thermal expansion; Conductors; Cranes; Gas insulated transmission lines; Ground support; Insulation; Power transmission lines; Substations; Thermal conductivity; Thermal expansion; Welding;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.107249
  • Filename
    107249