• DocumentCode
    1103611
  • Title

    Water treeing in service aged cables, experience and evaluation procedure

  • Author

    Steennis, E.F. ; Boone, W. ; Montfoort, A.

  • Author_Institution
    KEMA Lab., Arnhem, Netherlands
  • Volume
    5
  • Issue
    1
  • fYear
    1990
  • fDate
    1/1/1990 12:00:00 AM
  • Firstpage
    40
  • Lastpage
    46
  • Abstract
    Water treeing problems encountered in the Netherlands in some medium-voltage cables prompted in the authors to develop a test with which the degradation of the insulation of extruded cable could be characterized. The test method developed was demonstrated to be effective. It revealed that 20% of the network cables examined were defective and needed replacement. In evaluating the results, it was shown that the water tree susceptibility of some cables can be correlated with specific manufacturers or unknown parameters in their production process. However, it was not possible to attribute the cause of this susceptibility to the cross-linking process, conductor shields, or wet soils alone
  • Keywords
    ageing; cable insulation; electric breakdown of solids; organic insulating materials; polymers; power cables; Netherlands; XLPE insulation; conductor shields; cross-linking process; extruded cable insulation degradation; service aged MV cables; water tree susceptibility; wet soils; Aging; Cable insulation; Conductors; Degradation; Insulation testing; Manufacturing processes; Medium voltage; Production; Soil; Trees - insulation;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.107253
  • Filename
    107253