DocumentCode :
1107712
Title :
Cable Ampacity in Tray with Raised Covers
Author :
Engmann, Gary
Author_Institution :
Black & Veatch, Engineers-Architects Kansas City, Missouri
Issue :
2
fYear :
1986
fDate :
6/1/1986 12:00:00 AM
Firstpage :
113
Lastpage :
119
Abstract :
Power cable tray systems in generating stations are installed with tray covers that may be raised over the tray side rail. Raising the tray cover allows installation of the cover without cutting and fitting the cover around conduits that terminate at the tray. There is no industry standard or guidance for calculation of cable ampacity in trays with raised covers. The heat transfer literature is reviewed in this paper and the results of the review are incorporated in a method for calculation of cable ampacity in raised cover tray. Calculations are presented that show that cable ampacity with raised covers is approximately two percent greater than cable ampacity with covers installed directly on the tray side rails.
Keywords :
Cities and towns; Equations; Geometry; Heat transfer; Power cables; Power engineering and energy; Power generation; Rails; Railway engineering; Space heating;
fLanguage :
English
Journal_Title :
Energy Conversion, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8969
Type :
jour
DOI :
10.1109/TEC.1986.4765708
Filename :
4765708
Link To Document :
بازگشت