• DocumentCode
    1107712
  • Title

    Cable Ampacity in Tray with Raised Covers

  • Author

    Engmann, Gary

  • Author_Institution
    Black & Veatch, Engineers-Architects Kansas City, Missouri
  • Issue
    2
  • fYear
    1986
  • fDate
    6/1/1986 12:00:00 AM
  • Firstpage
    113
  • Lastpage
    119
  • Abstract
    Power cable tray systems in generating stations are installed with tray covers that may be raised over the tray side rail. Raising the tray cover allows installation of the cover without cutting and fitting the cover around conduits that terminate at the tray. There is no industry standard or guidance for calculation of cable ampacity in trays with raised covers. The heat transfer literature is reviewed in this paper and the results of the review are incorporated in a method for calculation of cable ampacity in raised cover tray. Calculations are presented that show that cable ampacity with raised covers is approximately two percent greater than cable ampacity with covers installed directly on the tray side rails.
  • Keywords
    Cities and towns; Equations; Geometry; Heat transfer; Power cables; Power engineering and energy; Power generation; Rails; Railway engineering; Space heating;
  • fLanguage
    English
  • Journal_Title
    Energy Conversion, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8969
  • Type

    jour

  • DOI
    10.1109/TEC.1986.4765708
  • Filename
    4765708