DocumentCode :
1107823
Title :
Influence of High Temperature Superconducting Transformer Geometry on Leakage Magnetic Field
Author :
Li, Xiaosong ; Wu, Suping ; Zhou, Yusheng ; Hu, Gui ; Long, Guzong
Author_Institution :
Changsha Univ. of Sci. & Technol., Changsha
Volume :
44
Issue :
4
fYear :
2008
fDate :
4/1/2008 12:00:00 AM
Firstpage :
492
Lastpage :
496
Abstract :
Leakage magnetic fields in high temperature superconducting (HTS) transformer windings reduce the critical current and increase the ac losses in HTS tapes. Moreover, because of the anisotropic properties of the HTS tapes, the influence of the radial component of the leakage field on critical current and ac losses is much stronger than that of the axial one. For these reasons, leakage magnetic fields must be carefully considered in HTS transformer design. In this paper, we report a study of the influence of the core structure and the winding configuration on the leakage field by the finite-element method (FEM), and offer some suggestions for reducing the maximal radial component of leakage field to make the HTS transformer more efficient.
Keywords :
critical currents; eddy current losses; finite element analysis; high-temperature superconductors; magnetic leakage; superconducting tapes; superconducting transformers; transformer windings; HTS tapes; ac losses; critical current; finite-element method; high temperature superconducting transformer windings; leakage magnetic fields; Finite-element method (FEM); HTS transformer; leakage magnetic field; transformer geometry;
fLanguage :
English
Journal_Title :
Magnetics, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9464
Type :
jour
DOI :
10.1109/TMAG.2007.915222
Filename :
4475340
Link To Document :
بازگشت