DocumentCode :
1107937
Title :
Integration of MHD Plants into Electric Utility Systems
Author :
Jackson, William D. ; Feero, William E. ; Seikel, George R. ; Gish, William B.
Author_Institution :
HMJ Corporation, P.O. Box 15128, Chevy Chase, MD 20815
Issue :
3
fYear :
1986
Firstpage :
26
Lastpage :
33
Abstract :
This paper considers the behavior of an MHD/steam-comined cylce plant under the dynamic operating conditions prescribed by the transient stability regime (50 msc to 10 sec after a disturbance on a power system). Using a three-phase fault to ground to test the model developed, it is shown that: (1) in this regime, the MHD generator acts as a current source to provide damping and consequent increased network stability; (2) the low energy storage capability of the MED generator reduces fault currents and plant surges relative to those of a similarly rated conventional plant; and (3) load tripping introduces special requirements which are discussed in the paper.
Keywords :
Damping; Energy storage; Magnetohydrodynamic power generation; Power industry; Power system dynamics; Power system faults; Power system modeling; Power system stability; Power system transients; Testing;
fLanguage :
English
Journal_Title :
Energy Conversion, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8969
Type :
jour
DOI :
10.1109/TEC.1986.4765730
Filename :
4765730
Link To Document :
بازگشت