Title :
Raccoon Mountain Pumped-Storage Plant - Ten Years Operating Experience
Author_Institution :
TENNESSEE VALLEY AUTHORITY, Chattanooga, Tennessee
Abstract :
Operational experience at the 1 530 MW Raccoon Mountain underground pumped-storage plant can be relevent to other large hydro facilities. A number of unusual features were incorporated and individual unit size was only recently overtaken elsewhere. Direct water cooling of rotor and stator windings has been successfully applied to salient pole machines. A number of problems, including difficulties with oil-filled 161 kV current transformers, and some mechanical aspects, are reported. Designed for remote supervisory control, the plant has required closer attention. Operating statistics are included.
Keywords :
Cooling; Costs; Current transformers; Lakes; Power generation; Reservoirs; Rivers; Statistics; Stator windings; Supervisory control;
Journal_Title :
Energy Conversion, IEEE Transactions on
DOI :