Maintaining balanced three-phase load voltage during single-phase auto-reclosing in medium voltage distribution lines
Author :
Basu, Kartik P. ; George, M.
Author_Institution :
Fac. of Eng., Multimedia Univ., Cyberjaya, Malaysia
Volume :
8
Issue :
5
fYear :
2014
fDate :
May-14
Firstpage :
798
Lastpage :
802
Abstract :
Single-phase auto-reclosing (SPAR) is used for restoring power supply to clear temporary single-phase to ground fault in medium-voltage distribution systems. A zigzag winding grounding transformer connected at the remotest load bus rebuilds the three-phase voltage during the SPAR dead time. A distribution system having more than one branch needs one zigzag transformer at the remotest end of each branch. Build-up three-phase voltage during SPAR is not balanced. Operation of distributed generator connected to the system during SPAR needs the voltage to be balanced. Magnitude of the negative sequence voltage may be reduced by connecting capacitor in series with the neutrals of each zigzag transformer.
Keywords :
earthing; power distribution faults; power distribution lines; transformer windings; SPAR dead time; balanced three-phase load voltage maintenance; distributed generator; distribution system; ground fault; medium voltage distribution lines; negative sequence voltage magnitude; power supply restoration; remotest load bus; single-phase auto-reclosing; zigzag winding grounding transformer;
fLanguage :
English
Journal_Title :
Generation, Transmission & Distribution, IET
Publisher :
iet
ISSN :
1751-8687
Type :
jour
DOI :
10.1049/iet-gtd.2013.0663
Filename :
6812259
Link To Document :
بازگشت