Analysis of a harmonic overvoltage due to transformer saturation following load shedding on Hydro-Quebec-NYPA 765 kV interconnection
Author
Bourgault, Omer ; Morin, Gaston
Author_Institution
Hydro-Quebec, Montreal, Que., Canada
Volume
5
Issue
1
fYear
1990
fDate
1/1/1990 12:00:00 AM
Firstpage
397
Lastpage
405
Abstract
An analysis is presented of the harmonic overvoltage recorded on the interconnection between Hydro-Quebec and the New York Power Authority (NYPA) in the Chateauguay area. The overvoltage was caused by transformer saturation, following tripping of the 765 kV transmission line linking both systems. EMTP (electromagnetic transient program) simulation yielded good agreement with field measurements and was valuable in reevaluating operating practices at the Chateauguay station
Keywords
load shedding; overvoltage; power system interconnection; power transformers; power transmission lines; 765 kV; Chateauguay area; EMTP simulation; Hydro-Quebec; NYPA; New York Power Authority; electromagnetic transient program; harmonic overvoltage; load shedding; power system interconnection; transformer saturation; transmission line; Circuit faults; EMTP; Electromagnetic measurements; Harmonic analysis; Joining processes; Power system harmonics; Power system interconnection; Power transmission lines; Transmission line measurements; Voltage control;