An Uninterruptible Power System as a Safety Related Isolation Device for Nuclear Power Plants
Author :
Gelazis, Valdas ; Griffith, David C. ; Kosarko, William
Author_Institution :
Cyberex, Inc., 7171 Industrial Park Blvd., Mentor, Ohio
Issue :
4
fYear :
1987
Firstpage :
513
Lastpage :
519
Abstract :
This paper describes the test procedure and results of a program to qualify a Class 1E uninterruptible power supply (UPS) as a power circuit isolation device between Class 1E power input sources and non-Class 1E load circuits for application in a nuclear power plant. Results demonstrate that the tested equipment provides suitable isolation and that the UPS is completely self-protecting as well as providing its normal UPS functions with automatic static bypass in the event of UPS failure or externally applied overload.
Keywords :
Batteries; Circuit faults; Circuit testing; Inverters; Power generation; Safety devices; Switches; System testing; Uninterruptible power systems; Voltage;
fLanguage :
English
Journal_Title :
Energy Conversion, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8969
Type :
jour
DOI :
10.1109/TEC.1987.4765886
Filename :
4765886