• DocumentCode
    1109887
  • Title

    Measurement and characterization of harmonic and high frequency distortion for a large industrial load

  • Author

    Girgis, Adly A. ; Clapp, Michael C. ; Makram, Elham B. ; Qiu, Jun ; Dalton, John G. ; Catoe, Ray C., Jr.

  • Author_Institution
    Dept. of Electr. & Comput. Eng., Clemson Univ., SC, USA
  • Volume
    5
  • Issue
    1
  • fYear
    1990
  • fDate
    1/1/1990 12:00:00 AM
  • Firstpage
    427
  • Lastpage
    434
  • Abstract
    A software package is described that was developed to perform harmonic analysis on digitized current and voltage waveforms. The authors also report on the measurement and characterization of voltage and current harmonics and high-frequency distortion of a large industrial load. Since waveform distortions often include periodic high-frequency transients, special signal processing techniques were developed in the software to alleviate misleading results of the calculated harmonics. From simultaneous measurements on all three phases, an investigation of harmonic unbalance at the industrial load is discussed. Problems with the installation of a capacitor bank for voltage regulation purposes are also described
  • Keywords
    electric distortion measurement; harmonic analysis; load (electric); power engineering computing; HF distortion measurement; capacitor bank; current harmonics; digitized current waveforms; digitized voltage waveforms; harmonic analysis; industrial load; signal processing techniques; software package; voltage harmonics; voltage regulation; Capacitors; Current measurement; Distortion measurement; Frequency measurement; Harmonic analysis; Harmonic distortion; Phase measurement; Signal processing; Software packages; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.107308
  • Filename
    107308