• DocumentCode
    1110435
  • Title

    Transients in Synchronous Machines with Balanced Capacitive Loads

  • Author

    Chen, Mo-Shing ; Duesterhoeft, W.C.

  • Author_Institution
    Arlington State College, Arlington, Texas
  • Volume
    83
  • Issue
    12
  • fYear
    1964
  • Firstpage
    1242
  • Lastpage
    1245
  • Abstract
    An analysis of the transient voltages and currents that occur when a balanced capacitance load is connected to a salient-pole alternator is presented. The 2-phase co-ordinate equations of Clarke, describing the ideal machine, are solved by means of the Laplace transform. Armature resistance and field saturation are neglected. Expressions result, giving amplitudes and frequencies of components of the transients.
  • Keywords
    Alternators; Armature; Capacitance; Chromium; Frequency; Laplace equations; Performance analysis; Synchronous machines; Transient analysis; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1964.4765968
  • Filename
    4765968