• DocumentCode
    1110686
  • Title

    Insulation Levels for VEPCO 500-Kv Substation Equipment

  • Author

    Wagner, C.L. ; Clayton, J.M. ; Young, F.S. ; Rudasill, C.L.

  • Author_Institution
    Westinghouse Electric Corporation, East Pittsburgh, Pa.
  • Volume
    83
  • Issue
    3
  • fYear
    1964
  • fDate
    3/1/1964 12:00:00 AM
  • Firstpage
    236
  • Lastpage
    241
  • Abstract
    A detailed study has been made of the Virginia Electric and Power Copmany (VEPCO) 500-kv transmission sytem to determine optimum insulation levels for the substation equipment. Results of this study depend on both economic and technical considerations. For the VEPCO system, a 70% arrester can be used at the generator step-up transformer locations, and a 75% will be required at step-down substations. Adequate impulse and switching surge margins permit a transformer BIL (basic impulse insulation level) of 1,300 kv to be used at all locations. The most practical circuit breaker BIL, consistent with good engineering practice and economy of application, is 1,550 kv.
  • Keywords
    Arresters; Design engineering; Lightning; Power generation economics; Power transformer insulation; Storms; Substations; Surge protection; Systems engineering and theory; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1964.4765992
  • Filename
    4765992