• DocumentCode
    1111034
  • Title

    Review of generator surge coordination including generator breakers

  • Author

    Dick, E.P. ; Dhirani, M.H. ; Gupta, Bineet Kumar ; Powell, P.W. ; Shinn, M. R A ; Greenwood, M.A. ; Porter, J.W.

  • Author_Institution
    Ontario Hydro, Toronto, Ont., Canada
  • Volume
    3
  • Issue
    2
  • fYear
    1988
  • fDate
    4/1/1988 12:00:00 AM
  • Firstpage
    599
  • Lastpage
    606
  • Abstract
    The results of a utility survey on surge protection practices for large generators are presented. The surge environment, 60 Hz withstand test value, designated impulse withstand, arrester protective levels, and insulation breakdown tests on two machines were compared. Factors included in the surge environmental were lightning, faults, HV switching, ferroresonance. opening surges, breaker failure, and system-side resonance. Several topics are identified for further study
  • Keywords
    electric generators; machine protection; surge protection; 60 Hz; HV switching; arrester protective levels; breaker failure; electric generator protection; faults; ferroresonance; generator breakers; generator surge coordination; impulse withstand; insulation breakdown; lightning; machine protection; opening surges; surge protection; system-side resonance; withstand test; Arresters; Capacitors; Impulse testing; Insulation testing; Power generation; Power transformer insulation; Resistors; Samarium; Surge protection; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/61.4297
  • Filename