DocumentCode :
1111034
Title :
Review of generator surge coordination including generator breakers
Author :
Dick, E.P. ; Dhirani, M.H. ; Gupta, Bineet Kumar ; Powell, P.W. ; Shinn, M. R A ; Greenwood, M.A. ; Porter, J.W.
Author_Institution :
Ontario Hydro, Toronto, Ont., Canada
Volume :
3
Issue :
2
fYear :
1988
fDate :
4/1/1988 12:00:00 AM
Firstpage :
599
Lastpage :
606
Abstract :
The results of a utility survey on surge protection practices for large generators are presented. The surge environment, 60 Hz withstand test value, designated impulse withstand, arrester protective levels, and insulation breakdown tests on two machines were compared. Factors included in the surge environmental were lightning, faults, HV switching, ferroresonance. opening surges, breaker failure, and system-side resonance. Several topics are identified for further study
Keywords :
electric generators; machine protection; surge protection; 60 Hz; HV switching; arrester protective levels; breaker failure; electric generator protection; faults; ferroresonance; generator breakers; generator surge coordination; impulse withstand; insulation breakdown; lightning; machine protection; opening surges; surge protection; system-side resonance; withstand test; Arresters; Capacitors; Impulse testing; Insulation testing; Power generation; Power transformer insulation; Resistors; Samarium; Surge protection; Voltage;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.4297
Filename :
4297
Link To Document :
بازگشت