Harmonic Composition of Low-Frequency Electromagnetic Emissions Associated with High-Voltage Transmission
Author
Daley, Michael L. ; Benitez, Henry ; Zajac, Herbert ; Chartier, Vernon
Author_Institution
Engineering Laboratory, Division of Neurosurgery, Oregon Health Sciences University, Portland, OR 97201
Issue
4
fYear
1985
Firstpage
227
Lastpage
228
Abstract
Electric-field-strength measures of the spectrum between 10 and 200 kHz were obtained under dry conditions near a 500-kV transmission line. Comparison of the magnitudes of electric field strength between the odd and even harmonics of 60 Hz revealed a marked asymmetry. The ratio of odd to even harmonic field strength ranged from 19 to 3.3. A primary source of these emissions may be produced by components within the power systems with nonlinearities that are best described by odd functions.