    Switching Surge Tests on Simulated and Full-Scale EHV Tower-Insulator Systems

  • Author

    Atwood, A.W. ; Hileman, A.R. ; Skooglund, J.W. ; Wittibschlager, J.F.

  • Author_Institution
    Southern California Edison Company, Los Angeles, Calif.
  • Volume
    84
  • Issue
    4
  • fYear
    1965
  • fDate
    4/1/1965 12:00:00 AM
  • Firstpage
    293
  • Lastpage
    303
  • Abstract
    Switching surge tests performed on simulated tower-insulator systems representative of possible 345- and 500-kV transmission line designs were performed so that line design parameters could be estimated for a specific value of switching surge overvoltage. Switching surge studies of the Southern California Edison Company (SCE) 500-kV transmission system dictated that the switching surge withstand strength for wet conditions should be 1065 kV. From the design-application curves, the center phase of the SCE 500-kV transmission tower-insulator system was designed to have a 12-foot 8-inch minimum horizontal strike distance and 27 insulators used in a 90-degree V-string configuration. Full-scale tower tests confirmed the switching surge design criteria.