DocumentCode
1112864
Title
Stability Studies and Tests on a 532-MW Cross-Compound Turbine-Generator Set
Author
Ewart, D.N. ; Landgren, G.L. ; Temoshok, M. ; Walkley, W.W.
Author_Institution
General Electric Company, Schenectady, N. Y.
Volume
84
Issue
4
fYear
1965
fDate
4/1/1965 12:00:00 AM
Firstpage
338
Lastpage
343
Abstract
In the fall of 1963, two extended steady-state stability tests were conducted on a 532 000-kW cross-compound steam turbine-generator at the Will County Station of the Commonwealth Edison Company. These tests followed a series of analytical studies conducted from 1961 through 1963, and aimed at predicting extended steady-state stability limits. In the 1950s, similar tests had been conducted on smaller tandem steam turbine-generators and on hydrogenerators. The subject report is the first documentation of tests conducted on cross-compound turbine-generator sets. In addition, studies and tests were conducted to confirm steady-state stability limits in the generator overexcited region (lagging power factor operation). Operation in this region may occur with extra long transmission lines or weak interconnections between the unit and the power system.
Keywords
Automatic voltage control; Documentation; Hydraulic turbines; Hydrogen; Power generation; Regulators; Shafts; Stability analysis; Steady-state; System testing;
fLanguage
English
Journal_Title
Power Apparatus and Systems, IEEE Transactions on
Publisher
ieee
ISSN
0018-9510
Type
jour
DOI
10.1109/TPAS.1965.4766201
Filename
4766201
Link To Document