Title
Duty Cycle Testing of Current Limiting Station and Intermediate Lightning Arresters
Author
Sakshaug, E.C. ; Carpenter, T.J. ; Stetson, E.W.
Author_Institution
General Electric Company, Pittsfield, Mass.
Volume
84
Issue
5
fYear
1965
fDate
5/1/1965 12:00:00 AM
Firstpage
422
Lastpage
425
Abstract
The testing of lightning arresters has been reasonably well defined by ASA C62.1-1962, but the comparatively recent development of current limiting arresters makes it necessary to re-examine some industry standards to determine whether they provide adequate proof of current limiting arrester performance. The duty cycle test requires revision because it does not subject lightning arresters to a rate-of-rise of current comparable with what might be obtained in service. Tests must be made with higher rates-of-rise to insure that failure of loss of protective characteristics will not occur under actual service conditions.
Keywords
Arresters; Current limiters; Frequency; Impulse testing; Lightning; Protective relaying; Surge protection; Valves; Voltage control; Zero voltage switching;