DocumentCode :
1113117
Title :
The Apple Grove 750-kV Project- 500-kV Switching Surge and Line Flashover Tests
Author :
Barnes, H.C. ; McElroy, A.J. ; Shankle, D.F. ; Smith, H.M.
Author_Institution :
American Electric Power Service Corporation, New York, N. Y.
Volume :
84
Issue :
7
fYear :
1965
fDate :
7/1/1965 12:00:00 AM
Firstpage :
550
Lastpage :
560
Abstract :
Rational design of extra-high-voltage systems depends on analytic studies to predict switching surge overvoltage magnitude and probability, and on laboratory tests for tower system switching surge withstand capability. Laboratory tests have been confined to ideal waveforms applied to single window configurations. Correlation with flashover performance of a typical 3-phase installation exposed to actual switching surge waveforms is attempted. The influence of interphase coupling and multiple circuit breaker operations in promoting multiphase flashover, which may curtail system performance margins, is also studied.
Keywords :
Circuit breakers; Circuit testing; Coupling circuits; Flashover; Laboratories; Poles and towers; Surges; System performance; System testing; Voltage control;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/TPAS.1965.4766228
Filename :
4766228
Link To Document :
بازگشت