• DocumentCode
    1113329
  • Title

    Power Transformers and Corona Testing

  • Author

    Vora, J.P. ; Foster, S.L.

  • Author_Institution
    Allis-Chalmers Manufacturing Co., Milwaukee, Wis.
  • Volume
    84
  • Issue
    8
  • fYear
    1965
  • Firstpage
    707
  • Lastpage
    714
  • Abstract
    There is an increased interest among transformer users in radio influence voltage measurements during routine commercial testing. This paper describes a procedure for determining the presence of corona under oil for transformers. An oscillographic record taken in conjunction with conventional radio influence voltage tests distinguishes between corona in oil which causes progressive deterioration of insulation and corona in air which does not. The data also shows that for high-voltage transformers, the transformer bushing with its capacitance tap provides a suitable coupling capacitor for radio influence voltage tests.
  • Keywords
    Capacitance; Capacitors; Corona; Insulation testing; Insulators; Oil insulation; Petroleum; Power transformer insulation; Power transformers; Voltage measurement;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1965.4766246
  • Filename
    4766246