DocumentCode :
1113329
Title :
Power Transformers and Corona Testing
Author :
Vora, J.P. ; Foster, S.L.
Author_Institution :
Allis-Chalmers Manufacturing Co., Milwaukee, Wis.
Volume :
84
Issue :
8
fYear :
1965
Firstpage :
707
Lastpage :
714
Abstract :
There is an increased interest among transformer users in radio influence voltage measurements during routine commercial testing. This paper describes a procedure for determining the presence of corona under oil for transformers. An oscillographic record taken in conjunction with conventional radio influence voltage tests distinguishes between corona in oil which causes progressive deterioration of insulation and corona in air which does not. The data also shows that for high-voltage transformers, the transformer bushing with its capacitance tap provides a suitable coupling capacitor for radio influence voltage tests.
Keywords :
Capacitance; Capacitors; Corona; Insulation testing; Insulators; Oil insulation; Petroleum; Power transformer insulation; Power transformers; Voltage measurement;
fLanguage :
English
Journal_Title :
Power Apparatus and Systems, IEEE Transactions on
Publisher :
ieee
ISSN :
0018-9510
Type :
jour
DOI :
10.1109/TPAS.1965.4766246
Filename :
4766246
Link To Document :
بازگشت