• DocumentCode
    1113433
  • Title

    A Study of Corona Discharge Rate and Energy Loss in Spark Gaps

  • Author

    Bartnikas, R. ; D´Ombrain, G.L.

  • Author_Institution
    Northern Electric Company Ltd., Ottawa, Ont., Canada
  • Volume
    84
  • Issue
    9
  • fYear
    1965
  • Firstpage
    770
  • Lastpage
    779
  • Abstract
    A study was carried out on the corona discharge rate and energy loss occurring within artificial cavities. An air gap with metallic electrodes was utilized to simulate the ionization sources within a cable. The corona discharge rates, obtained with varying gap spacings under different vapor pressures, showed marked deviations from the idealized behavior. thhe calculated tangent ¿ values, in terms of the pulsed corona energy loss for the tested cable-cavity combinations, were found to agree reasonably with those determined experimentally.
  • Keywords
    Cable insulation; Corona; Electrodes; Energy loss; Fault location; Ionization; Power cables; Pulse measurements; Spark gaps; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Apparatus and Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0018-9510
  • Type

    jour

  • DOI
    10.1109/TPAS.1965.4766256
  • Filename
    4766256