DocumentCode
1116562
Title
Design considerations for the Eddy County static VAr compensator
Author
Tyll, H.K. ; Huesmann, G. ; Habur, G. Huesmann K ; Stump, K. ; Elliott, W.H. ; Trujillo, F.E.
Author_Institution
Siemens AG, Erlangen, Germany
Volume
9
Issue
2
fYear
1994
fDate
4/1/1994 12:00:00 AM
Firstpage
757
Lastpage
763
Abstract
This paper describes the steps for the design of the static VAr compensator at (SVC) Eddy County. The specified system requirements on operating range, loss evaluation and harmonic performance led to an SVC configuration which contains one thyristor switched capacitor (TSC) branch, one thyristor controlled reactor (TCR) branch for continuous reactive power control and two double tuned filter branches. The system voltage of the SVC secondary bus was optimized to 8.5 kV based on thyristor equipment capabilities. The paper shows the voltage and current stresses of the thyristor valves taking into account system faults for the TCR branch and misfiring effects on the TSC branch. The approach for filter design considering the harmonic performance requirements and resulting component ratings are shown. The Eddy County SVC commenced commercial operation in April 1992
Keywords
compensation; power capacitors; power systems; reactors (electric); static VAr compensators; thyristor applications; Eddy County; continuous reactive power control; current stress; double tuned filter branches; harmonic performance; loss evaluation; misfiring effects; operating rang; secondary bus; static VAr compensator; thyristor controlled reactor; thyristor equipment capabilities; thyristor switched capacitor; thyristor valves; voltage stress; Capacitors; Control systems; Inductors; Performance loss; Power harmonic filters; Power system harmonics; Reactive power control; Static VAr compensators; Thyristors; Voltage;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/61.296254
Filename
296254
Link To Document