Title :
Understanding the impacts of moisture and thermal ageing on transformer´s insulation by dielectric response and molecular weight measurements
Author :
Saha, T.K. ; Purkait, P.
Author_Institution :
Univ. of Queensland, Brisbane
fDate :
4/1/2008 12:00:00 AM
Abstract :
Properties of oil and paper in a transformer degrade primarily due to thermal ageing and moisture ingress. Dielectric diagnostic tests, such as Recovery Voltage (RV), and Polarizations and Depolarization Current (PDC) measurement are currently being explored as potential tools for insulation condition assessment. A modern chemical analysis tool for paper molecular weight (MW) measurement, Gel Permeation Chromatography (GPC) or the more accurately described Size Exclusion Chromatography (SEC) promises to be useful in assessing ageing condition. However, the issue of separately assessing the impacts of ageing and moisture on oil and paper has been a key issue for many years. In the current research project, a series of experiments have been performed under controlled laboratory conditions with preset moisture content, and at controlled high temperature ageing. Whereas RV and PDC measurement results were found to be more sensitive to the moisture content of the oil and paper insulation, the MW distribution measurement by SEC provided a trend of insulation thermal ageing. This paper first provides a brief description of RVM, PDC and SEC procedures followed by a description of the experimental techniques adopted. Results are then analysed with the view of separately understanding the impacts of thermal ageing and moisture on the condition of oil and paper insulation in a transformer.
Keywords :
ageing; chromatography; dielectric measurement; insulation testing; paper; power transformer insulation; power transformer testing; transformer oil; chemical analysis; dielectric diagnostic tests; gel permeation chromatography; high temperature ageing; molecular weight measurements; mositure content; paper insulation; polarization and depolarization current measurement; recovery voltage measurement; size exclusion chromatography; thermal ageing; transformer oil; Aging; Dielectric measurements; Dielectrics and electrical insulation; Moisture control; Moisture measurement; Oil insulation; Petroleum; Power transformer insulation; Temperature control; Weight measurement; Condition monitoring, gel permeation chromatography, moisture content, moisture related degradation, molecular weight, polarization and depolarization current, return voltage, size exclusion chromatography, thermal ageing, transformer condition assessment;
Journal_Title :
Dielectrics and Electrical Insulation, IEEE Transactions on
DOI :
10.1109/TDEI.2008.4483479