DocumentCode :
1122740
Title :
The Measurement of Reactive Energy in Polluted Distribution Power Systems: An Analysis of the Performance of Commercial Static Meters
Author :
Cataliotti, Antonio ; Cosentino, Valentina ; Nuccio, Salvatore
Author_Institution :
Dipt. di Ing. Elettr., Elettron. e delle Telecomun. (D.I.E.E.T.), Univ. di Palermo, Palermo
Volume :
23
Issue :
3
fYear :
2008
fDate :
7/1/2008 12:00:00 AM
Firstpage :
1296
Lastpage :
1301
Abstract :
This paper presents a comparative analysis of the performances of both a traditional induction meter and various types of commercial static meters for reactive energy in the presence of harmonic distortion. This is a topical issue, since there are several types of static meters on the market, based on different principles of construction. In accordance with current standards, these meters are designed to operate in sinusoidal conditions and their performance is not tested in the presence of harmonic distortion. However, with the increase of pollution levels in power systems, the meters may be used even in the presence of distorted voltages and/or currents; in such cases, their accuracy may be very different from the nominal conditions, and the various meters may lead to different measurements of energy for the same load conditions. In this paper, the analysis is supported by several experimental tests, performed by means of a power calibrator.
Keywords :
distribution networks; harmonic distortion; power measurement; power meters; power system harmonics; power system measurement; reactive power; commercial static meters; distorted currents; distorted voltages; harmonic distortion; polluted distribution power systems; power calibrator; reactive energy measurement; Energy measurements; induction meters; power systems harmonics; reactive power; static meters;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2008.919239
Filename :
4483687
Link To Document :
بازگشت