An Experimental Validation of Lightning Performance in Distribution Lines
Author
Miyazaki, Teru ; Okabe, Shigemitsu ; Sekioka, Shozo
Author_Institution
Tokyo Electr. Power Co., Yokohama
Volume
23
Issue
4
fYear
2008
Firstpage
2182
Lastpage
2190
Abstract
The Tokyo Electric Power Company had conducted field research of voltages and currents in actual distribution lines due to lightning strokes between 1997 and 2001. These results confirm that the distribution line faults are mainly caused by direct lightning strokes to the line. Thus, it is important to simulate lightning performance for direct strokes to establish a lightning protection design of distribution lines. In this paper, statistical data of the observed voltages and currents are analyzed, and the validation of the observation results for the direct lightning strokes using a lightning surge analysis model is conducted. The observation results and the simulation model are useful in clarifying lightning performance in distribution lines.
Keywords
distribution networks; lightning protection; power system faults; power transmission lines; Tokyo Electric Power Company; direct lightning strokes; distribution line faults; lightning current; lightning performance; lightning protection design; lightning surge analysis model; soil ionization; statistical data; Direct lightning stroke; distribution line; lightning current; lightning protection design; lightning surge analysis model; soil ionization;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2008.919252
Filename
4483700
Link To Document