• DocumentCode
    1126683
  • Title

    A Universal Fault Location Technique for N-Terminal ({N}\\geq q 3) Transmission Lines

  • Author

    Liu, Chih-Wen ; Lien, Kai-Ping ; Chen, Ching-Shan ; Jiang, Joe-Air

  • Author_Institution
    Dept. of Electr. Eng., Nat. Taiwan Univ., Taipei
  • Volume
    23
  • Issue
    3
  • fYear
    2008
  • fDate
    7/1/2008 12:00:00 AM
  • Firstpage
    1366
  • Lastpage
    1373
  • Abstract
    This paper presents a universal fault location technique for N-terminal transmission lines based on synchronized phasor measurement units. The development of the technique is based on two-terminal fault location technique. The proposed algorithm is different from traditional multiterminal fault location techniques. We apply two-terminal fault location technique to N-terminal transmission lines and propose a novel fault section selector/fault locator. The proposed method has a very good tolerance. The proposed approach provides an analytical solution and its computational burden is very low since it does not require iterative operations. An extensive series of simulations were conducted to verify the accuracy of the proposed algorithm. The average fault location error under various fault conditions is well below 1%.
  • Keywords
    fault location; iterative methods; phase measurement; power transmission faults; power transmission lines; N-terminal transmission lines; analytical solution; iterative operations; section selector-fault locator; synchronized phasor measurement units; universal fault location technique; Fault location; multiterminal transmission lines; phasor measurement units (PMUs);
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2008.919244
  • Filename
    4484951