DocumentCode
1126683
Title
A Universal Fault Location Technique for N-Terminal
Transmission Lines
Author
Liu, Chih-Wen ; Lien, Kai-Ping ; Chen, Ching-Shan ; Jiang, Joe-Air
Author_Institution
Dept. of Electr. Eng., Nat. Taiwan Univ., Taipei
Volume
23
Issue
3
fYear
2008
fDate
7/1/2008 12:00:00 AM
Firstpage
1366
Lastpage
1373
Abstract
This paper presents a universal fault location technique for N-terminal transmission lines based on synchronized phasor measurement units. The development of the technique is based on two-terminal fault location technique. The proposed algorithm is different from traditional multiterminal fault location techniques. We apply two-terminal fault location technique to N-terminal transmission lines and propose a novel fault section selector/fault locator. The proposed method has a very good tolerance. The proposed approach provides an analytical solution and its computational burden is very low since it does not require iterative operations. An extensive series of simulations were conducted to verify the accuracy of the proposed algorithm. The average fault location error under various fault conditions is well below 1%.
Keywords
fault location; iterative methods; phase measurement; power transmission faults; power transmission lines; N-terminal transmission lines; analytical solution; iterative operations; section selector-fault locator; synchronized phasor measurement units; universal fault location technique; Fault location; multiterminal transmission lines; phasor measurement units (PMUs);
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2008.919244
Filename
4484951
Link To Document