Boiler plant control using a minimum order dynamic pole placement compensator
Author
Anakwa, Winifred K N ; Swamy, M.N.S.
Author_Institution
Dept. of Electr. Eng., Concordia Univ., Montreal, Que., Canada
Volume
35
Issue
1
fYear
1988
fDate
2/1/1988 12:00:00 AM
Firstpage
113
Lastpage
118
Abstract
A quadratic performance index with a prescribed degree of stability is used to select the desired closed loop poles of a boiler plant in a 150 MW power station. Using only the available output variables for feedback. Fortran computer programs are written to design a dynamic compensator of minimum order p to achieve placement of the desired closed loop poles. The plant and the dynamic output feedback controller are simulated on a CDC Cyber 170-835 digital computer. The performance of the boiler plant controlled by the dynamic compensator is compared to performances under observer-based and state feedback controllers
Keywords
boilers; compensation; digital simulation; power stations; 150 MW; CDC Cyber 170-835 digital computer; Fortran computer programs; boiler plant control; feedback; minimum order dynamic pole placement compensator; observer-based controllers; power station; quadratic performance index; stability; state feedback; Boilers; Linear feedback control systems; Mathematical model; Observers; Output feedback; Performance analysis; Riccati equations; Stability; State estimation; State feedback;
fLanguage
English