DocumentCode
1137019
Title
Induced Voltages on Long Aerial and Buried Pipelines Due to Transmission Line Transients
Author
Kopsidas, Konstantinos ; Cotton, Ian
Author_Institution
Sch. of Electr. & Electron. Eng., Univ. of Manchester, Manchester
Volume
23
Issue
3
fYear
2008
fDate
7/1/2008 12:00:00 AM
Firstpage
1535
Lastpage
1543
Abstract
In a previous paper , the voltage induced onto a 1-km above-ground pipeline by transmission line transients was shown to be significant in comparison to the induced voltage resulting from power system currents. This paper enhances the previous work in three distinct areas. First, both aerial and buried pipelines are considered. Above-ground pipelines are shown to be more at risk from transient-induced voltages. Second, parallelisms of up to 10 km are simulated. The results show that increasing parallelisms do not result in higher induced voltages once a critical distance has been reached. Third, a backflashover from a tower in the vicinity to a pipeline is modeled. This allows conductive coupling to take place at the same time as inductive and capacitive coupling. Backflashovers are shown to be an important consideration in determining the maximum voltages observed on a nearby pipeline.
Keywords
flashover; pipelines; transmission lines; backflashovers; capacitive coupling; long aerial-buried pipelines; power system currents; transient-induced voltages; transmission line transients; Lightning; pipelines; switching transients; transmission lines;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.2007.916234
Filename
4493401
Link To Document