• DocumentCode
    1137019
  • Title

    Induced Voltages on Long Aerial and Buried Pipelines Due to Transmission Line Transients

  • Author

    Kopsidas, Konstantinos ; Cotton, Ian

  • Author_Institution
    Sch. of Electr. & Electron. Eng., Univ. of Manchester, Manchester
  • Volume
    23
  • Issue
    3
  • fYear
    2008
  • fDate
    7/1/2008 12:00:00 AM
  • Firstpage
    1535
  • Lastpage
    1543
  • Abstract
    In a previous paper , the voltage induced onto a 1-km above-ground pipeline by transmission line transients was shown to be significant in comparison to the induced voltage resulting from power system currents. This paper enhances the previous work in three distinct areas. First, both aerial and buried pipelines are considered. Above-ground pipelines are shown to be more at risk from transient-induced voltages. Second, parallelisms of up to 10 km are simulated. The results show that increasing parallelisms do not result in higher induced voltages once a critical distance has been reached. Third, a backflashover from a tower in the vicinity to a pipeline is modeled. This allows conductive coupling to take place at the same time as inductive and capacitive coupling. Backflashovers are shown to be an important consideration in determining the maximum voltages observed on a nearby pipeline.
  • Keywords
    flashover; pipelines; transmission lines; backflashovers; capacitive coupling; long aerial-buried pipelines; power system currents; transient-induced voltages; transmission line transients; Lightning; pipelines; switching transients; transmission lines;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.2007.916234
  • Filename
    4493401