Abstract :
The effects of frequency dependence, line asymmetry, and varying ground conductivity on ultrahigh speed, travelling wave based, single ended, protection schemes are investigated. Typical schemes assume the transmission lines to be balanced and frequency independent which simplifies the analysis of the fault transients. Investigation of a single circuit vertically configured transmission line reveals that better results can be obtained by using modal parameters based on the configuration of the transmission line. The problem of modal mixing at discontinuities on the transmission line is demonstrated in the case of an unbalanced line to ground fault. The results described have applications in both protection and fault location schemes
Keywords :
fault location; power system protection; power transmission lines; fault location; frequency dependence; line asymmetry; line parameters; modal mixing; modal parameters; protection; single circuit; single ended travelling wave; transmission lines; unbalanced line; varying ground conductivity; vertically configured transmission line;
fLanguage :
English
Journal_Title :
Generation, Transmission and Distribution, IEE Proceedings C
Publisher :
iet
ISSN :
0143-7046
Type :
jour
Filename :
149577
Link To Document :
بازگشت