Abstract
The effect of design changes on the contact resistance of overlapping bolted/pad joints was investigated. It was found that slanting the edges of the bus-bars/pads under 45° and making slots in the overlapping areas significantly reduce the contact resistance of a joint and improve its mechanical integrity. These improvements are results of enlarged contact area and creation of a uniform current distribution at the contact interface.
Keywords
contact resistance; current distribution; electric connectors; lubrication; substations; surface treatment; HV power connectors; bolted high-power connectors; connection design; contact interface; contact resistance; enlarged contact area; high power overlapping bolted joints; lubrication; overlapping bolted/pad joints; substation components; uniform current distribution; Conductors; Connectors; Contact resistance; Distributed parameter circuits; Maintenance; Power generation economics; Power transmission lines; Surface contamination; Surface resistance; Switching circuits;