DocumentCode :
1145996
Title :
Energy recovery filter with variable quality factor
Author :
Jiang, Xiao ; Gole, A.M.
Author_Institution :
Dept. of Electr. & Comput. Eng., Manitoba Univ., Winnipeg, Man., Canada
Volume :
9
Issue :
3
fYear :
1994
fDate :
7/1/1994 12:00:00 AM
Firstpage :
1625
Lastpage :
1631
Abstract :
This paper presents further investigations into using an energy recovery (ER) filter for mitigating harmonic instabilities in integrated AC/DC power systems. For certain system conditions, a low quality factor (Q) filter is desirable and for other conditions a high Q is better. This inspired the concept of a “controllable Q filter” in which the power absorbed in the filter is controllable by electronic means. The controllable Q filter uses an ER link so that this power is recovered. The investigations are conducted through computer simulation using an electromagnetic transient simulation program. The CIGRE benchmark model is selected as the base system. The results show that the controllable Q filter helps the system recover from faults
Keywords :
Q-factor; control system analysis computing; digital simulation; filters; power system analysis computing; power system control; power system harmonics; power system interconnection; power system restoration; power system stability; CIGRE benchmark model; computer simulation; controllable Q filter; electromagnetic transient simulation program; energy recovery filter; faults; harmonic instabilities; integrated AC/DC power systems; power system recovery; variable quality factor; Computer simulation; Erbium; Frequency; HVDC transmission; Impedance; Inverters; Power harmonic filters; Q factor; Resonance; Student members;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/61.311201
Filename :