DocumentCode :
1146107
Title :
Distribution Surge Arrester Behavior Due to Lightning Induced Voltages
Author :
Yokoyama, Shigeru
Author_Institution :
Central Research Institute of Electric Power Industry Tokyo, Japan
Volume :
1
Issue :
1
fYear :
1986
Firstpage :
171
Lastpage :
178
Abstract :
Using a calculation program for the analysis of lightning induced voltages on a multi-conductor system, the protection effects of surge arresters on three-phase distribution lines were studied. Installation of surge arresters every 200 meters provides a 6.6 kV distribution line with good protection effects. Even severe lightning induced voltage will not create large arrester discharging currents.
Keywords :
Arresters; Conductors; EMTP; Insulation; Lightning; Power distribution lines; Power system protection; Power system transients; Surge protection; Voltage;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.1986.4307904
Filename :
4307904
Link To Document :