Synthetic Testing Method for Generator Circuit Breakers
Author :
Thuries, E. ; Van Doan, P. ; Dayet, J. ; Joyeux-Bouillon, B.
Author_Institution :
Alsthom-Atlantique Villeurbanne, France
Volume :
1
Issue :
1
fYear :
1986
Firstpage :
179
Lastpage :
184
Abstract :
Today, generator circuit breakers are air-blast circuit breakers, mainly to cope with the non zero passage current requirements. Their breaking capacity is extremely high (275 kA/24 kV). The testing station power is not always great enough to perform a complete testing through a direct circuit. The low ohmic value parallel resistor in those breakers makes it difficult to perform the synthetic tests. The authors bring forward a rather simple circuit arrangement to test at one time the breaking capacity of the main chamber. They wish to demonstrate the effectiveness of the testing method with an arc model.
Keywords :
Circuit breakers; Circuit testing; Laboratories; Nuclear power generation; Performance evaluation; Power generation; Protection; Resistors; Switches; Voltage;