Title :
Harmonics from SVC transformer saturation with direct current offset
Author :
Xu, W. ; Martinich, T.G. ; Sawada, J.H. ; Mansour, Y.
Author_Institution :
British Columbia Hydro, Vancouver, BC, Canada
fDate :
7/1/1994 12:00:00 AM
Abstract :
Circulation of direct current in transformer windings can cause significant transformer saturation and harmonic generation. This problem may be experienced by static VAr compensators with an anti-parallel thyristor arrangement. This paper presents a technique to analyze the harmonic distortions caused by transformer saturation with direct current offset. The technique is used to investigate the harmonic generation from the transformer of a static VAr compensator to be installed in the BC Hydro system
Keywords :
compensation; power control; power system harmonics; power transformers; reactive power; static VAr compensators; thyristor applications; transformer windings; BC Hydro system; SVC transformer saturation; anti-parallel thyristor arrangement; direct current offset; equivalent circuits; harmonic generation; static VAr compensators; Circuit faults; Circuit simulation; DC generators; Frequency conversion; Harmonic analysis; Magnetic flux; Power system harmonics; Power transformers; Static VAr compensators; Thyristors;
Journal_Title :
Power Delivery, IEEE Transactions on