Abstract
An unusual case of difficult application of surge protective devices was solved by field measurements with retrofit of protective devices suitable for the particular environment. Onsite measurements indicated that capacitor switching transients were causing excessive current surges in the varistors and fuses protecting the input to a thyristor motor drive. Knowledge of the environment gained by the measurements allowed understanding of the problem and specification of matching surge protective devices.
Keywords
Capacitors; Current measurement; Fuses; Motor drives; Particle measurements; Surge Protective Devices - c62; Surge protection; Surges; Thyristors; Varistors;