DocumentCode
1146432
Title
Interrupting Test of 275kV Reactor and Its Evaluation in Three Kinds of Gas-Blast Circuit Breakers
Author
Kobayashi, A. ; Ishizuka, H. ; Takahashi, N. ; Yanabu, S. ; Uehara, K.
Author_Institution
Toshiba Corporation Kawasaki, Japan
Volume
1
Issue
2
fYear
1986
fDate
4/1/1986 12:00:00 AM
Firstpage
87
Lastpage
94
Abstract
By using a 275kV, 150MVA reactor, interrupting tests, were conducted on an opening resistor-fitted air-blast circuit breaker, a two-pressure SF6 gas-blast circuit breaker, and a puffer-type. SF6 gas circuit breaker. Maximum overvoltages generated on the reactor were 1.95 PU with the puffer-type SF6 gas circuit breaker, 2.27 PU with the two-pressure SF6 gas-blast circuit breaker, and 1.71 PU with the opening resistor-fitted air-blast circuit breaker. The test results indicated that arc voltage had a great effect on overvoltage. With the puffer-type SF6 gas circuit breaker, overvoltage was low particularly during short arc times, and high only in the vicinity of the 0.5 cycle corresponding to maximum arc time. A digital calculation of overvoltage waveforms by using nonlinear arc voltage represented by base arc voltage and a normal function revealed that arccontained interruptions could be simulated very well.
Keywords
Capacitance; Circuit breakers; Circuit testing; Inductance; Inductors; Resistors; Senior members; Sulfur hexafluoride; Surges; Voltage;
fLanguage
English
Journal_Title
Power Delivery, IEEE Transactions on
Publisher
ieee
ISSN
0885-8977
Type
jour
DOI
10.1109/TPWRD.1986.4307938