DocumentCode :
1146443
Title :
Estimation of Restriking Transient Overvoltage on Disconnecting Switch for GIS
Author :
Ogawa, S. ; Haginomori, E. ; Nishiwaki, S. ; Yoshida, T. ; Terasaka, K.
Author_Institution :
The Tokyo Electric Power Co., Inc. Tokyo, Japan
Volume :
1
Issue :
2
fYear :
1986
fDate :
4/1/1986 12:00:00 AM
Firstpage :
95
Lastpage :
102
Abstract :
On an actual 550kV GIS (gas-insulated switchgear), the restriking surges of disconnecting switches at a high frequency of several MHz were successfully measured by employing two different methods. Further, by comparing the measured waveforms with waveforms obtained through calculations, it has been proved that restriking surge of disconnecting switches can be estimated by conducting calculations with considerably high accuracy. Also included, in this paper are certain suggestions regarding GIS simulation methods to be adopted for the calculations, while concurrently reported are the results of calculations on 111 circuit configurations at 10 different GIS´s.
Keywords :
Circuit breakers; Circuit simulation; Frequency measurement; Gas insulation; Geographic Information Systems; Surges; Switches; Switchgear; Switching circuits; Voltage control;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.1986.4307939
Filename :
4307939
Link To Document :
بازگشت