DocumentCode
1146736
Title
Development and Field Test on a Distribution Line Carrier Communication System
Author
Miyahara, Akira ; Mine, Ikuo ; Watanabe, Atsumi ; Sakou, Eisaburo ; Nukiyama, Makoto
Author_Institution
Kyushu Electric Power Co., Inc. (Fukuoka, Japan)
Volume
1
Issue
3
fYear
1986
fDate
7/1/1986 12:00:00 AM
Firstpage
28
Lastpage
34
Abstract
A communication system through distribution lines was developed for distribution automation. This system consists of a two level hierarchy system : a zero-phase-sequence carrier communication system through ungrounded 6kV distribution lines and an earth return communication system through grounded 100V/200V lines. In each system, transmission signals are generated by switching a passive element of small capacity between a line and the ground, and the signals are circulated through the line and the ground. By using this method, the influence of load impedance change and noises generated in loads is avoided sufficiently. Field tests were carried out at Ijiri Substation of the Kyushu Electric Power Co., Inc. for one year starting in September 1983. High reliability of the system was verified in terms of endurance in a severe environment and data transmission performance.
Keywords
Automation; Communication switching; Data communication; Impedance; Noise generators; Power system reliability; Signal generators; Substations; System testing; Working environment noise;