DocumentCode
1146908
Title
Recommended Dielectric Tests and Test Procedures for Converter Transformers and Smoothing Reactors
Author
Kennedy, W. N. ; Crichton, C. C. ; Cillies, D. A. ; Criffard, W. F. ; Fischer, H. C. ; Hurty, C. ; Lampe, W. ; Pobbins, C. A. ; Stein, W. W. ; Yasuda, Eliana
Author_Institution
General Electric Company
Volume
1
Issue
3
fYear
1986
fDate
7/1/1986 12:00:00 AM
Firstpage
161
Lastpage
166
Abstract
The dielectric conditions which are unique to converter transformers and smoothing reactors are examined. Both steady state and transient situations are discussed. Two additional tests are recommended for this equipment - a long term dc applied potential test and a polarity reversal test. Formulae are developed to calculate proposed test levels, and guidelines are presented concerning allowable partial discharge levels during the tests.
Keywords
Bridge circuits; Dielectrics; HVDC transmission; Impulse testing; Inductors; Pulse transformers; Rectifiers; Smoothing methods; Steady-state; Stress;