DocumentCode :
1147223
Title :
Multiprocessor UHV Line Relay Testing with Transient Network Analyzer
Author :
St-Jacques, Alain ; Lemay, Jean ; MacDonald, Richard
Author_Institution :
Institut de recherche d´´Hydro-Québec (IREQ) Varennes, Québec, Canada
Volume :
1
Issue :
3
fYear :
1986
fDate :
7/1/1986 12:00:00 AM
Firstpage :
370
Lastpage :
375
Abstract :
Since field evaluation does not provide sufficient data for detailed performance analysis, the multiprocessor-based UHV line relay developed at IREQ was tested on a Transient Network Analyzer (TNA). Results obtained from approximately 80,000 fault simulations revealed unpredicted behavior that had passed unnoticed during previous digital simulation and laboratory investigations. Special hardware and software designed for relay testing on the TNA are presented with examples. The final test session applied to the corrected relay showed that all faults generated within the reach of 80% of the line length are cleared in less than 1.5 cycles by the impedance algorithm alone.
Keywords :
Circuit faults; Digital relays; Digital simulation; Hardware; Laboratories; Performance analysis; Power system transients; Protective relaying; Testing; Transient analysis;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.1986.4308017
Filename :
4308017
Link To Document :
بازگشت