DocumentCode
1147397
Title
Stability of DBPC Inhibited Oil in Oil Circuit Recloser Operation [includes discussion]
Author
Oura, Kazumi ; Hazelwood, R.Nichols ; Frey, Raymond M.
Author_Institution
ASSOCIATE MEMBER AIEE, Line Material Company, Milwaukee, Wis., a McGraw Electric Company Division.
Volume
72
Issue
2
fYear
1953
Abstract
The stability of transformer oil inhibited with 2,6-di-tertiary-butyl-paracresol (DBPC) under arcing conditions in oil circuit reclosers has been studied. Oil containing 0.3 per cent DBPC and the uninhibited base oil were subjected to arcing in 15-kv distribution-class oil circuit reclosers. Studies were made of the oil properties to determine the comparative stability of the inhibited and uninhibited oils. It is concluded that there is no essential difference in the stability of oil inhibited with 0.3 per cent DBPC and uninhibited oil under arcing conditions.
Keywords
Circuit stability; Explosions; Hazards; Inhibitors; Interrupters; Petroleum; Seals; Shafts; Switches; Testing;
fLanguage
English
Journal_Title
Power Apparatus and Systems, Part III. Transactions of the American Institute of Electrical Engineers
Publisher
ieee
ISSN
0097-2460
Type
jour
DOI
10.1109/AIEEPAS.1953.4498636
Filename
4498636