• DocumentCode
    1147659
  • Title

    Development of New Diagnostic Method for Hot-Line XLPE Cables with Water Trees

  • Author

    Oonishi, H. ; Urano, F. ; Mochizuki, T. ; Soma, K. ; Kotani, K. ; Kamio, K.

  • Author_Institution
    The Tokyo Electric Power Co., Inc. Tokyo, Japan
  • Volume
    2
  • Issue
    1
  • fYear
    1987
  • Firstpage
    1
  • Lastpage
    7
  • Abstract
    A new insulation diagnostic method for XLPE cables containing water trees is presented. A dc component in the ac charging current of these cables was found to be a significant sign of the existence of water trees. The dc component has good correlations with such insulation characteristics of aged XLPE cables as ac breakdown voltage and dc leakage current. Criteria for insulation diagnosis of 6.6kV XLPE cables have been established. An automatic insulation diagnostic device has been developed. It is now being applied to hot-line XLPF cables in distribution systems of TEPCO (The Tokyo Electric Power Co., Inc.).
  • Keywords
    Aging; Cable insulation; Conductors; Current measurement; Dielectrics and electrical insulation; Leakage current; Manufacturing; Testing; Trees - insulation; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.1987.4308065
  • Filename
    4308065