DocumentCode :
1147710
Title :
Signal Propagation on Single Phase Power Distribution Lines at Power Line Carrier Frequencies
Author :
Hemminger, R.C. ; Gale, L.J. ; O´Neal, J.B., Jr.
Author_Institution :
Westinghouse Electric Corp. Raleigh, NC
Volume :
2
Issue :
1
fYear :
1987
Firstpage :
28
Lastpage :
35
Abstract :
Two sets of propagation measurements were made on a 20,847 foot unenergized power distribution line in the frequency range 0 to 50 kHz. The line was configured with and without distribution transformers. From the first set of measurements a voltage transfer function was calculated for this line. In the second set of measurements the line was energized with a 25 kHz signal and the voltage, current and impedance were measured along the line. Various propagation characteristics such as attenuation, characteristic impedance, velocity of propagation, and standing wave ratios were determined from these measurements.
Keywords :
Current measurement; Energy measurement; Foot; Frequency measurement; Impedance measurement; Power distribution lines; Power measurement; Transfer functions; Transformers; Voltage measurement;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.1987.4308069
Filename :
4308069
Link To Document :