Title
The Effect of Distribution Transformers on Distribution Line Carrier Signals
Author
Hemminger, Rodney C. ; Gale, L.J. ; Amoura, F. ; O´Neal, J.B.
Author_Institution
Westinghouse Electric Corp. Raleigh, NC
Volume
2
Issue
1
fYear
1987
Firstpage
36
Lastpage
40
Abstract
A study is made of the primary impedance of single phase power distribution transformers at frequencies of 2-50 kHz. This band includes the frequencies used for distribution line communications. A range of primary impedance values is found as the secondary impedance varies between 1 and 100% of full load. Then the effect of these transformers on the attenuation, phase constant and characteristic impedance of a power distribution line is computed. Calculations are compared with measurements reported elsewhere.
Keywords
Attenuation; Distributed computing; Frequency; Impedance; Load flow control; Meter reading; Optical propagation; Power distribution lines; Power transformers; Signal processing;