DocumentCode :
1147806
Title :
Metallic Particle Motion in 3-Phase SF6 Gas Insulated Bus
Author :
Yanabu, S. ; Okubo, H. ; Matsumoto, S. ; Aoyagi, H. ; Kobayashi, N.
Author_Institution :
Toshiba Corporation Kawasaki, Japan
Volume :
2
Issue :
1
fYear :
1987
Firstpage :
101
Lastpage :
106
Abstract :
To investigate the behavior of metallic particles in 3-phase gas insulated buses (3-phase GIB), we conducted a test by using a 3-phase 275kV, ac, 60Hz full-scale model. The test results revealed that in a 3-phase electric field, unlike in a single-phase field, metallic particles were trapped on and around the high-voltage conductors and revolved circumferentially. Computer analysis shows that it was closely related to locational and periodic changes in the electric field provided by the 3-phase GIB, and that there were points on the high-voltage conductors in which metallic particles were readily trapped. It also was proved that phenomena peculiar to the 3-phase GIB could be reproduced very well by computer simulation.
Keywords :
Aluminum; Conductors; Dielectrics and electrical insulation; Gas insulation; Geographic Information Systems; Motion measurement; Particle measurements; Sulfur hexafluoride; Testing; Voltage;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.1987.4308079
Filename :
4308079
Link To Document :
بازگشت