DocumentCode :
1147898
Title :
Optimum Shunt Capacitor for Power Factor Correction at Busses with Lightly Distorted Voltage
Author :
Saleh, Roham T. ; Emanuel, Alexander E.
Author_Institution :
Worcester Polytechnic Institute Worcester, Massachusetts 01609
Volume :
2
Issue :
1
fYear :
1987
Firstpage :
165
Lastpage :
173
Abstract :
The goal of this paper is to determine the effect of time variation of system impedances and voltage harmonics on the value of optimum capacitor for power factor correction at busses with nonsinusoidal voltage. Two types of 24 hours time-variation of voltage harmonices and Thevenin impedance are assumed. The equivalent load impedance is also considered time variable and assumed to contain a large proportion of induction motors. The daily energy losses are computed and graphed in function of the shunt capacitance used for power factor correction. The results of this study indicate that in order to avoid resonances and to find the optimum capacitor the time variation of harmonics and system impedances must be known as precise as possible.
Keywords :
Capacitance; Harmonic distortion; Impedance; Milling machines; Power capacitors; Power factor correction; Power system harmonics; Reactive power; Substations; Voltage;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.1987.4308087
Filename :
4308087