• DocumentCode
    1148929
  • Title

    The Incidence of Lightning Strikes to Power Lines

  • Author

    Eriksson, A.J.

  • Author_Institution
    National Electrical Engineering Research Institute Council for Scientific and Industrial Research Pretoria, South Africa
  • Volume
    2
  • Issue
    3
  • fYear
    1987
  • fDate
    7/1/1987 12:00:00 AM
  • Firstpage
    859
  • Lastpage
    870
  • Abstract
    This paper addresses the lightning attractive radius concept and procedures for estimating the number of lightning flashes to power lines. Empirical data - drawn from extensive observations of lightning incidence upon various practical structures (including lines) - are related to a simple analytical model of the striking process, and a generalised expression for estimating strike incidence is presented. Comparison of the new expression with current practice, suggests that the latter may lead to underestimations of more than 50% in the height range 10 - 30 m, and additionally, that expected strike incidence to taller structures could be overestimated by 30% or more.
  • Keywords
    Africa; Analytical models; Councils; Earth; Equations; Genetic expression; Lightning; Senior members; Uncertainty; Wires;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.1987.4308191
  • Filename
    4308191