• DocumentCode
    1149061
  • Title

    Development of Compact 500 kV 8000 a Gas Insulated Transmission Line-Dust Control during Field Jointing and Method for Detecting Conductive Particles

  • Author

    Kaminaga, K. ; Koshiishi, M. ; Hayashi, T. ; Matsuki, M. ; Hara, T. ; Sugiyama, N.

  • Author_Institution
    The Tokyo Electric Power Co., Inc. Tokyo, Japan
  • Volume
    2
  • Issue
    4
  • fYear
    1987
  • Firstpage
    961
  • Lastpage
    968
  • Abstract
    This paper describes the results of studies made on dust control during field jointing and a method for detecting conductive particles after installation in the development of a compact 500 kV 8000 A gas insulated transmission line (GIL). The study on dust control during field jointing proved that field jointing of the compact GIL can be done like conventional GIL in an easily fabricated vinyl shelter without a clean air flow. Harmful conductive particles can be detected with an Acoustic Emission (AE) sensor. This sensor is effective in improving the reliability of the compact GIL when used with a suitable ac voltage during field test. A 120 m long test line of compact 500 kV 8000 A GIL was constructed and, in a long-term field test, proved to have properties sufficient for practical use.
  • Keywords
    Acoustic sensors; Acoustic signal detection; Acoustic testing; Atmosphere; Conductors; Gas detectors; Gas insulated transmission lines; Gas insulation; Sulfur hexafluoride; Voltage;
  • fLanguage
    English
  • Journal_Title
    Power Delivery, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8977
  • Type

    jour

  • DOI
    10.1109/TPWRD.1987.4308207
  • Filename
    4308207